Options adapt to the selected source water — pool and cooling sources lock to their own duty; uses that don’t apply are greyed out.
If TSS is unknown it is estimated from turbidity (≈1.5×NTU). If both are blank, a default for the source water is used.
Applies a margin to the design solids load. Use for bores where iron oxidises before the filter, or surface water subject to rain events. Where iron/manganese removal is the duty, note the media manufacturer recommends >45 m/h backwash.
2 · Vessel Arrangement
Coarse suits heavy solids / roughing duty (backwash 40–45 m/h). Standard backwash 30–45 m/h. Fine adds Grade 0 for sub-micron capture (Crypto barrier) and fluidises at 20–30 m/h. Per manufacturer recommendations, max 45 m/h.
⚠ A manual design velocity is entered below — vessel count and model are locked to Auto so the tool can match the requested velocity. Clear the velocity field to unlock them.
FRP vessels rated 6 bar max operating pressure. Water temperature envelope 10–30 °C assumed.
Valve selected on flow and thread size, not tank size (per Runxin). 2.5" valve heads (F71/F67) fit 4" tank openings with a thread reducer. The valve, not the bed, often limits backwash.
Leave blank for automatic selection. Manual entry (8–30 m/h) overrides the water-quality and duty recommendation — vessel count and model then lock to Auto so the tool can find the closest design to the requested velocity. Design flow is always maintained.